CHARGING AND MONITORING UNIT FOR LEAD ACID BATTERIES IN FLOAT SERVICE

General features

  • Allows systems with lead acid batteries in float service to be in compliance with EN54
  • Constant current battery charger
  • Electromagnetic compatibility according to EN50081-2 and EN50082-2 (Industrial Environment)
  • Battery disconnection at the end of discharge; alarm   20 sec. earlier
  • Battery decoupled from the load through an high efficiency device
  • Overload protection of the battery
  • Automatic test to check the battery state of charge
  • Battery disconnected or discharged signal
  • Protected against battery polarity reversal, overloads and short circuits
  • Output is floating versus case

 

Product Data Sheet Download Pdf

 

For more information

If you don’t find the product you are looking for here, send us an email to infosecap@secap.it, or ring us up at 02-9055758. We’ll take a look together at the best solutions for your requirements.

FC512K

INPUT VOLTAGE:

10-15 Vdc

INPUT CURRENT:

≤ 30 A

NOMINAL OUTPUT VOLTAGE: 12V

NOMINAL OUTPUT CURRENT: 2,5 A

NOMINAL POWER: 30 W

FC524K

INPUT VOLTAGE:

20-30 Vdc

INPUT CURRENT:

≤ 30 A

NOMINAL OUTPUT VOLTAGE: 24V

NOMINAL OUTPUT CURRENT: 2,5 A

NOMINAL POWER: 60 W

FC548K

INPUT VOLTAGE:

40-60 Vdc

INPUT CURRENT:

≤ 20 A

NOMINAL OUTPUT VOLTAGE: 48V

NOMINAL OUTPUT CURRENT: 1,5 A

NOMINAL POWER: 72 W